Description / remarks:
Used Mycom/Mayekawa industrial heat pump with only 1.800 operating hours . This in condition as new industrial heat pump installation is composed of the following main components and built on 2 separate steel frames:
- 1 piece Mycom piston compressors type N6HS (direct driven) equipped with:
Siemens 315kW E-motor IP55
Capacity control by means of Danfoss frequency inverter iP55 and valve lift
Oil separator
Oil cooler - glycol cooled
Oil pump
Cylinder head Cooling - glycol cooled
All necessary safety devices and pressure gauge panel
- Water-cooled condenser with sub cooler, consisting of
1 piece Vatherus heat exchanger type PSHE 5/4HH-278/4/1, Q - plate
1 piece Vatherus heat exchanger type PSHE 3HH-136/1/1, Q - plate
- 1 piece Polar NH3 separator +25°C, volume 2034Ltr complete with 2 pieces liquid floats
- Switch box
- All necessary stop valves, valves and pressure certificates
Heating capacity of 1678kW is with the refrigerant R717/Ammonia at an evaporating temp. of +30°C and a condensation temp. of +72°C absorbed power of 239kW. Water outlet temp. of +70°C / inlet temp. of +24°C at 32,2m3/h.