Brand |
|
Type |
|
kW |
|
Description |
|
Year |
|
More info |
DWM/Copeland / Helpman |
|
storage / freeze Installation -60°C/-65°C, type of refrigerant: R23+R404A |
|
14 kW |
|
Used, very special low temperature DWM/Copeland/Helpman storage/freezing installation (cascade system) and consists of the following main components:
• Cascade central compressor unit, consists of:
1 x semi-hermetic DWM low pressure compressor, working with refrigerant R23 at evaporating temperature of -68°C
2 x semi-hermetic high pressure compressors, working with refrigerant R404A at evaporating temperature -30°C
• 2 x Helpman single sided blowing low temperature evaporators with each 2 pieces ventilators of 750W, electrical defrost, air flow 10.400m3/h, dimensions 210 x 110x 70 cm and weight 110kg
• 1 x Helpman double sided blowing evaporator for the production room(sluice) -20°C ambient temp. with 3 ventilators of 250W, electrical defrost, air flow 5.400m3/h, dimensions 345 x 170 x 59cm, weight 325kg with a cooling capacity of 28kW at evaporating temperature of -30°Cl
• 1 x Helpman air-cooled condenser with copper/seawater resistant fin coils
• Switch-board
• Under-pressure and over-pressure valves
Mentioned cooling capacity is with the refrigerant R23+R404a at -68°C/-30°C, -30°C/+40°C.
This installation is suitable for a freeze storage of approx. 600m3with a storage temperature of -60°C to -65°C, very suitable for tuna storage.
|
|
2001 |
|
More information |
Frigotronic / Copeland |
|
HSB-CU-120/2 SCR used refrigerator/freezing equipment, type of refrigerant: R404A/507 |
|
20 kW |
|
Nice used Cool/Freeze installation for cooling a cool or freeze room, equipped with the following main components: condensing unit for outdoor installation, consisting of air-cooled condenser, 2 pieces scroll compressor and control box. This unit will be delivered with 2 pieces of Goedhart cool / freeze evaporators type FC385BP502-7-230E with electric defrosting and with a fin spacing of 7 mm. Mentioned cooling capacity of 20 kW is at an evaporating temperature of -30°C with a refrigerant. R404a/507 Cooling capacity at an evaporating temperature of -10°C is approximately 40 kW.
|
|
2006 |
|
More information |
Bitzer |
|
used freeze- and cold store installations |
|
56 kW |
|
Used and in very well condition: a complete Bitzer cool/freeze installation to cool a big cool or freeze room.
|
|
2000 |
|
More information |
Bitzer |
|
HSN 7471-75-40R Bitzer storage freezing installation, type of refrigerant: R404A/All Freon |
|
83 kW |
|
Used and in very good maintained condition (always maintained by GEA) storage freezing installation, brand Bitzer/Goedhart. This storage freezing installation will be composed of the following main components:
• 1 piece Bitzer screw package type HSN 7471-75-40R
• Bitzer screw package is equipped with oil separator, air-cooled oil cooler, closed intercooler for subcooling liquid coupled to the eco. compressor, Bitzer liquid tank of 180L
• Suction manifold with suction filter
• Manometer set low/high pressure with all necessary safety devices
• Complete control box with Eliwell step controller
• 5 pieces Goedhart VCI-B-82508EF freeze storage evaporators with electric defrost
• Cabero air-cooled condenser type ACHSD099MB / 2L-26D, year of 2016
Mentioned cooling capacity is with the refrigerant R404a/R507 at -30°C /+40°C.
This installation is suitable for a deep-freeze storage of approx.. 4000m3 storage space with a storage temperature of -20°C.
|
|
2005/2016 |
|
More information |
Bitzer/Goedhart |
|
used cool/ freeze installation, type of refrigerant: R507 |
|
100 kW |
|
Used, in very good condition complete Bitzer/Goedhart cooling/freezing combination (very suitable for 0°C, -10°C, -20°C storage temperatures) and consists of the following main components:
• 2 pieces Bitzer cool/freeze units with each:
2 pieces Bitzer 4P-15.2Y-40P compressors
1 piece 6J-33.2Y-40P compressor
• 10 pieces Goedhart cooling/freezing evaporators, type VNS-65457 with electrical defrost and each 5 pieces WOODS ventilators 220V/310Watt
• 1 piece Goedhart air-cooled condenser type KOAL-M66 710.6P with 2 separate sections
• Switch-board
Mentioned cooling capacity of 100kW is with the refrigerant R507 at evaporating temperature of -30°C.
Cooling capacity at an evaporating temperature of -10°C is 248kW.
|
|
2004 |
|
More information |
Bitzer/Searle/GEA |
|
complete cooling plant, type of refrigerant: R404A /All Freon |
|
112 kW |
|
Used complete Bitzer/ Searle/GEA cooling plant-/installation. This in very good condition complete cooling plant is composed of the following main components:
• Bitzer piston package consists of
1 piece Bitzer piston compressor type 6H-35.2Y (frequency controlled at 60Hz)
1 piece Bitzer piston compressor type 4G-20.2Y
Oil separator, Vertical liquid tank, high/low pressure gauges with all necessary safety devices
• 3 pieces Searle/GEA dual-discharge blowing cooling-/freezing evaporators type LSR122-64-4D-EL, each with air volume 3,6m3/s, fin spacing 4mm, electrical defrost
• 2 pieces Searle/GEA dual-discharge blowing cooling-/freezing evaporators type DSR100-4L each with air volume 1,7m3/s, fin spacing 4mm, electrical defrost
• 1 piece Searle/GEA one-sided blowing cooling evaporator type DSR100-4L with air volume 2,7m3/s, fin spacing 4mm, electrical defrost
• 1 piece Searle/GEA air-cooled condenser type MEC234-N604D AL
• Complete control cabinet with Danfoss frequency controller
Mentioned cooling capacity of 112kW is with the refrigerant R404 at -8°C/+45°C.
|
|
2011 |
|
More information |
Bitzer |
|
used cold store installation |
|
118 kW |
|
Used and in very good condition: a complete refrigeration installation to cool a big cold room or corridor. The installation consists of the following main components: Bitzer 6F 50.2Y-40P tank aggregate, switch-board, separate Güntner condenser, 5 pieces two sided blowing Güntner evaporators. Mentioned cooling capacity is at 0°C evaporating temperature. Installation is built in 1993, compressor manufactured in 2003.
|
|
1993 / 2003 |
|
More information |
GEA/Grasso/Goedhart |
|
used complete freezing installation, type of refrigerant: R717/Ammonia |
|
138 kW |
|
Used complete GEA/Grasso/Goedhart storage freezing installation. This in very good condition complete freezing installation is composed of the following main components:
• GEA/Grasso piston package consists of
1 piece GEA/Grasso two stage piston compressor type RC4212 (direct driven)
Schorch 90kW E-motor 1000RPM
Oil separator
• 3 pieces Goedhart one-sided blowing freezing evaporators type VRB 63638, each with stainless steel coil, air volume 37.717m3/h, fin spacing 8mm, hot gas defrosting in coil and drip tray
• Low 1 pressure separator, brand GEA/Prevesco, volume 1425Ltr with 1 piece Witt liquid pomp
• 1 piece Goedhart air-cooled condenser type FEAL-90M/4-6P
• Complete control cabinet with PLC
• All necessary control stations, stop valves, liquid valves, floats with brands such as Danfoss, Parker, Witt
Mentioned cooling capacity of 138kW is with the refrigerant R717/ammonia at -32°C/+30°C at 1000RPM.
|
|
2000 |
|
More information |
Bitzer/Goedhart |
|
used freeze- and cold store installation, type of refrigerant: R404A/507 |
|
246 kW |
|
Used in very good maintained condition: complete Bitzer/Goedhart cool/freeze installation consisting of the following main components; 1 x Bitzer unit for outside use with built in 1 x Bitzer central unit with 4 pieces 6H 25.2Y compressors (capacity control 0-33%-66%-100%) with an oil flow-back system and oil floaters on the carters of the compressors. Separately is delivered a Profroid air-cooled condenser type C7AH 10 MD4-12 PS (528 kW at DT15 K) with 10 ventilators. Switchboard cabinet with the complete control system. Furthermore, this cool/freeze installation is equipped with 4 pieces Goedhart PLK evaporators 21 kW ∆T 8 at an evaporating temperature of -10°C and with 2 pieces Woods ventilators of each 0,83 kW and 6 pieces PLK evaporators 31,5 kW ∆ 8-10°C with 3 pieces ventilators of 0,83 kW each. Complete hotgas defrosting set. If desired we can can also supply these evaporators with electrical defrost. Mentioned cooling capacity is with the refrigerant R404 at -10°C evaporating and +40°C condensing. Freezing capacity at -30°C evaporating is 104 kW.
Cooling capacity:
At -10°C evaporating temperature 246 kW / at -30°C evaporating temperature 104 kW.
|
|
2004 |
|
More information |
Bitzer / Heplman |
|
used cooling installation, type of refrigerant: R507 |
|
373 kW |
|
Used complete Bitzer / Helpman cooling installation for processing rooms and or corridors. This in very good maintained condition cooling installation consists of the following main components:
• Bitzer cooling plant (built in a 10 ft container for outdoor installation), equipped with 3 pieces 6F-50.2Y compressors, oil separator, switch-board, liquid tank
• Helpman / Alfa-Laval air-cooled condenser type HTC-100-253-410-CT-400V
• 14 pieces Helpman double-sided evaporators type Thor-D-436-7-L-42 / 5-220V
• P&ID drawing and the necessary certificates
Mentioned cooling capacity is at an evaporating temperature of 0 ° C.
|
|
2005 |
|
More information |
Grasso/GEA/Baltimore |
|
used industrial NH3/CO2 cooling plant/frozen storage installation, type of refrigerant: R717/CO2 |
|
560 kW |
|
Used industrial cooling/freezing installation brand Grasso / GEA / Baltimore. This fine and very well maintained cooling/freezing installation with a capacity of 560 kW (840 kW with 3 compressors) -6°C/CO2 and 150 kW -33°C/CO2 is composed of the following main components:
• 3 pieces NH3 Grasso/GEA direct driven piston compressors type V 600 of which 1 stand-by, each equipped with ABB 100kW E-motor frequency-controlled, latest GEA controller. Capacity each compressor is 365kW at -8°C/+32°C with an absorbed power 79kW.
• 2 pieces Baltimore hybrid evaporating condensers type CXVE 151 0809-10L. Capacity each condenser is 547kW at wet bulb temp. of +21°C and condensation temp. of +32°C.
• Hansen Air Purger.
• Horizontal -10°C NH3 separator, internally connected to the cascade CO2 condenser with natural CO2 circulation -6°C.
• Horizontal -6°C CO2 liquid separator complete with 2 pieces hermetic CO2 liquid pumps.
• Oil equalizer tank (collection system) connected to the NH3 separator with automatic return system.
• -33°C CO2 frozen storage plants 150 kW with 3 pieces Dorin CO2 piston compressor -33°C/-6°C.
• 10 pieces Coolers and Condensers evaporators type pump circulation CO2, equipped with 3 pieces ventilators (3 x 0,39kW), hot glycol defrosting. Capacity is 33 kW at evaporating temp. of -4°C at air inlet temp. of +2°C.
• 6 pieces Coolers and Condensers evaporators type pump circulation CO2, equipped with 2 pieces ventilators (2 x 1,77kW), hot glycol defrosting. Capacity is 38 kW at evaporating temp. of -4°C at air inlet temp. of +2°C.
• 4 pieces Coolers and Condensers evaporators type pump DX CO2, equipped with 2 pieces ventilators (2 x 0,6kW), electric defrosting. Capacity is 17,5 kW at evaporating temp. of -31°C at air inlet temp. of -25°C.
• Switchboard cabinet with Siemens S7/Simatic touchscreen, Danfoss frequency controller for the 3 pieces Grasso/GEA compressors and the fans of the Baltimore condensers.
|
|
2015 |
|
More information |
Bitzer |
|
complete cooling plant, type of refrigerant: R404A/All Freon |
|
581 kW |
|
Used and in condition as new (only 1150 hours in production) complete Bitzer cooling installation consists of the following main components:
• Bitzer cooling plant (built in an isolated container for outdoor application ) equipped with:
3 pieces Bitzer screw packages type HSK 7461-80, each package with 63 kW E-motor, oil filter, low-/high pressure gauges, low-/ high pressure switch,
Central oil separator
Vahterus heat exchanger type PHSE-3LL-108-1/1 for liquid subcooling
Complete control cabinet
• Central liquid vessel
• Evapco evaporating condenser type ATC-M252E with frequency controlled fan motor
• Refrigeration and electrical drawings
Mentioned cooling capacity of is with the refrigerant R404a at -3°C/ +35°C with an absorbed power 154 kW.
Cooling capacity at -10°C / +35°C is 435 kW.
|
|
2011 |
|
More information |